4-20mA Sensor Interface Primer

From Phidgets Legacy Support
Revision as of 22:44, 20 December 2011 by Mparadis (talk | contribs) (Created page with "Things this page should cover: '''4-20 mA sensors:''' * 4-20 mA is an electrical standard for connection sensors to a data acquisition device. * 2 wires are used, one wire to po...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

Things this page should cover:

4-20 mA sensors:

  • 4-20 mA is an electrical standard for connection sensors to a data acquisition device.
  • 2 wires are used, one wire to power the sensor and the other wire is a"ground".
  • The sensor sends data by changing the amount of current it consumes
  • This is not very efficient, but it is much more immune to noise, and can be used for long distances between sensor an DAQ.
  • 4-20 mA sensors often run off high voltages, often 12-24v but check sensor data sheet to be sure
  • 4-20 mA sensors are typically expensive and industrial. There are often 0-5v versions available.
  • Why to use 4-20mA sensors?
    • You have one already
    • You want to do a really long run of wire
    • Environment has lots of EMI
    • Sensor is only available in 4-20 mA format

Advantages:

  • If wire is broken, no current is consumed (sensor returns 0 A), normal operation is minimum 4mA, therefore failure is obvious.
  • Q: the Phidget 4-20 mA adapter can only supply 15V? What if my sensor needs 24V?
    • A: Use 24v external power supply, hook + side to sensor and - side to ground on 1018. The 15V on the 1132 is left unused.